Audio-Visual Nurse-Call System with voice intercom capability. U.L. 1069 Listed. The NC150N masters can be flush, surface or desk mounted with the proper housing.

The Alpha Communications®/Tektone NC150N series audio-visual nurse-call system is designed for health-care applications where voice communication and visual indication is required. The NC150N system can support up to two (2) master stations per system. When a remote station is activated, the NC150N annunciator will sound an electronic tone and will light, indicating the location of the call. The tone signal can be silenced at the master station (and/or at the optional LI150B remote duty station(s) for non-emergency calls). The individual switch/light will remain lighted until the remote station is reset at the point of origination, or when answered by voice from the master station (for remotes with voice capability only). The NC150N master annunciator is modular and can be flush, surface or desk mounted, and is available in any size, in multiples of four (4) lights/switches. The NC150N features built-in tone signal, and tone silence button and light. Model ST005D 'TEST' buttons are used on each annunciator lamp module for lamp testing. A press-to-talk button enables the NC150N master to speak with any voice type remote station. Each NC150N master has a built-in amplifier with voice volume controls. An optional model TA150N handset, can be installed onto any master station, for private voice communication, or for very noisy environments.


NC150N Series Nurse-Call System

NC150N Series
FEATURES


• Modular (NC150N) Master Station available for any size application (in multiples of 4
lights/switches)
• Built-in Electronic Tone Signal and Tone Silence Switch (Tone Silence Over-Ride for
Emergency-Calls)
• Wide Variety of Remote Pullcords/Push-button Stations
• Single or Dual NC150N Master Station Capability
• Ideal for Hospital and Nursing Home Applications - U.L. 1069 Listed.
• Optional Remote Annunciators can be provided
• Master(s) can be Flush, Surface or Desk Mounted
ARCHITECTS' AND ENGINEERS' SPECIFICATIONS


The audio-visual nurse-call system shall be Alpha Communications®/Tektone NC150N series, or approved equal. At each of the bed locations, contractor shall furnish and install a model IR151B (single) or IR152B (dual) bedside station and the required SF301/8 call-cords (or other specialty type cords as required). At each bath location, contractor shall furnish and install a model SF155B (push/pull) or SF337C (shower type) emergency-call station. At each remote location, contractor shall furnish and install a model LI381 corridor dome light. Where required, contractor shall furnish and install the necessary LI382 corridor zone light(s), and/or model IR150B staff stations.

At the main nurse's location, contractor shall furnish and install one (1) model NC150N/xxx (xxx=number of lamp indicators-must be in multiples of 4) annunciator with appropriate backbox (specify flush, surface or desk mounting). Annunciator shall have indicator lights no less than 5/8" by 5/8" in size, to allow for positive room recognition, when activated. Unit shall have model ST005D test button(s) to allow for testing of all indicator lamps, as often as desired. Each NC150N master station shall have a built-in voice amplifier with internal volume controls. System shall be U.L. listed 1069 to the latest standards. Contractor shall observe all local and national electrical codes.

WIRING REQUIREMENTS:

See system wiring diagram no. IL380 for more complete wiring information.