Nurse-Call/Emergency-Call Masters

Ideal for monitoring any dry contact type closure (norm. open or closed circuit type) The DS100 masters can be flush, surface or desk mounted with the proper housing.

The Alpha Communications®/Tektone DS100 Door Sentry™ series latching annunciator is designed for alarm indications of an opening or a closing of a dry contact, or for other emergency-call or panic type applications.

When a remote contact switch is activated, the DS100 annunciator will sound an electronic alarm (tone) and will light, indicating the location of the alarm. The tone signal can be silenced at the master station (and/or at the optional IR019B remote alarm indicator). The individual switch/light will remain lighted until the remote switch is reset, and the master switch is depressed twice, resetting the light at the master annunciator.

The DS100 master annunciator is modular and can be flush, surface or desk mounted, and is available in any size, in multiples of four (4) lights/switches. The DS100 features built-in tone signal speaker, and tone silence button and light. Model ST005D 'TEST' buttons are optional, but strongly recommended for lamp testing, on each annunciator module.


DS100 Series Latching Annunciators

DS100 Series
FEATURES
  • Modular (DS100) Master Station available for any size application (in multiples of 4
    lights/switches)
  • Built-in Electronic Tone Signal and Tone Silence Switch
  • Wide Variety of Remote Pullcords/Push-button Stations
  • Form 'C' Dry Contact Relay output to power remote devices
  • Ideal for Elderly Housing and Emergency-Call Applications
  • Individual selector switches can be disabled (shunted) at the master station(s)
  • Optional Remote Annunciators can be provided
  • Requires only 1-Common and 1-Selective wire to each remote contact switch assembly

    ARCHITECTS' AND ENGINEERS' SPECIFICATIONS
    The latching annunciator system shall be Alpha Communications®/Tektone Door Sentry™ DS100 series, or approved equal. At each of the remote locations, contractor shall furnish and install the required open --OR-- closed circuit contact switch assembly.

    At the main security location, contractor shall furnish and install one (1) model DS100/xxx (xxx=number of lamp indicators-must be in multiples of 4) annunciator console with appropriate backbox (specify flush, surface or desk mounting). Annunciator shall have indicator lights no less than 5/8" by 5/8" in size, to allow for positive alarm recognition, when activated. Unit shall have model ST005D test button(s) to allow for testing of all indicator lamps, as often as desired. Annunciator shall be latching type, and indicator lights will remain lighted until reset at the master (once remote switch has also been reset). Unit shall work on normally open OR normally closed switches, but all switches must be of the same activation/configuration/type.

    REQUIRED COMPONENTS:
    S1 Scrulox Screw Driver. Required for annunciator installation and maintenance.
    N553A Lamp Extraction Tool. One (1) recommended for each master annunciator station. It allows easy extraction of any annunciator bulb (#LI014) that may have burned out.
    DS100 Master Control module with tone speaker, tone-off light and tone-off button. One (1) required at each master station location. Requires one or more PM023/4 4-lamp add- on modules and annunciator frame/housing. Can handle up to 5- PM023/4 modules.
    AM100 Blank module. Used when more than 5- PM023/4 lamp modules are needed. Each AM100 module can handle up to 9- PM023/4 lamp modules.
    ST005D Test Button. Required on each DS100 and/or each AM100 module that has any of the PM023/4 lamp modules.
    PM023/4 4-Lamp Modules. One (1) required for each master station, for each four (4) or less indicating locations required. Up to five (5) PM023/4's can be installed onto a DS100 module and up to nine (9) PM023/4's can be installed onto an AM100 mod- ule. Each module that has any PM023/4 lamps should have the ST005D test button.
    RP021CM Lens Caps and Custom Markings. Four (4) are required for each PM023/4 module.
    PK2019 Controller Unit. One (1) required for each master annunciator station. Requires SS106 transformer for power.
    SS106 16/24VAC Transformer. One (1) required to power each PK2019 control unit.
    OF200 Series Annunciator Frame. One (1) required for each master station. Use with OH200 series flush housing --OR-- OH300 series surface back box --OR-- IH300 series desk cabinet. Multiple frames and housings may be used for larger master stations.
    OH200 Series Flush Housing. One (1) required for each master station. Use with OF200 series master annunciator frame, for flush mounting.
    ------OR------
    OH300 Series Surface Back Box. One (1) required for each master station. Use with OF200 series master annunciator frame, for surface mounting.
    ------OR------
    IH300 Series Desk Cabinet. One (1) required for each master station. Use with OF200 series master annunciator frame, for desk top mounting.
    ------AND------
    Open or Closed Circuit Switch contacts (provided by the customer). NOTE: switches can be either open or closed circuit type, but all of the switches on a master must be the same type!!

    OPTIONAL COMPONENTS:
    LI381 Emergency Dome Light. One (1) required for each apartment, or remote signaling that requires a hallway light indicator. White ABS plastic with white bulb cover. Mounts over two (2) gang electrical back box. Includes 24 volt white bulb.
    IR019B Remote Indicator. One (1) required if you need to have a remote tone signal sound at a location, other than the master(s), when an alarm signal has activated. Mounts over two (2) gang electrical back box. Stainless steel faceplate with Tone-Off button.

    WIRING REQUIREMENTS:
    See system wiring diagram no. AWD040 for more complete wiring information.